Unistrut P3300T 1-5/8'' x 7/8'' Slotted Channel, 12 Gauge

Sku:

P3300T

UOM: LGT

Product Details

Unistrut's P3300T channel is commonly used for trapeze supports, seismic bracing, ceiling grids, pipe, conduit, duct and cable tray supports, racks, and other general framing. For application examples, refer to our Application Showcase. Product dimensions are 1 5/8" wide x 7/8" tall x 12 ga. thick. Slots are sized for a 1/2" threaded rod or fastener. This slotted option is popular because it's adjustable, yet has modest load capacity loss versus the solid version. It has 85% of the capacity of the solid version of the profile. Our P3300T is available in Pre-Galvanized (PG), Unistrut Defender (DF), Hot-Dip Galvanized (HG), Plain (PL), Green (GR), ZInc Dichromate (ZD), Stainless Steel (SS or ST) and Aluminum (EA).


Unistrut Buffalo is a division of Eberl Iron Works, Inc.

 

     

More Information
Pricing SKU P3300T-10PL
SKU P3300T
Pack Size Length
UOM LGT
Brand Unistrut

MATERIAL

Unistrut channels are accurately and carefully cold formed to size from low-carbon strip steel.

All spot-welded combination members, except P1001T, are welded 3" (76 mm) maximum on center.

STEEL: PLAIN

12 Ga. (2.7 mm), 14 Ga.(1.9 mm) and
16 Ga. (1.5 mm) ASTM A1011 SS GR 33

STEEL: PRE-GALVANIZED

12 Ga. (2.7 mm), 14 Ga. (1.9 mm) and
16 Ga. (1.5mm) ASTM A653 GR 33

For other materials, see Special Metals or Fiberglass sections.

FINISHES

All channels are available in:

  • Perma Green III (GR)
  • Pre-galvanized (PG), conforming to ASTM A653 G90
  • Hot-dipped galvanized (HG), conforming to ASTM A123
  • Plain (PL)
  • Unistrut Defender™ (DF), conforming to ASTM A1046

*** Perma Green finish is a commercial grade finish, and as such scuffs and scratch marks are to be expected. If a flawless finish is desired, it is recommended to apply a matching touch up paint ***

DIMENSIONS

Imperial dimensions are illustrated in inches. Metric dimensions are shown in millimeters and rounded to one decimal place.

STANDARD LENGTHS

Standard lengths are 10 feet (3.05m) and 20 feet (6.10m). Tolerances are ±1⁄8" (3 mm). Special lengths are available for a small cutting charge with a tolerance of ±1⁄8" (3 mm).

CURVED CHANNEL

Contact your local Unistrut Service Center or Unistrut Corporation for more information.

LOAD DATA

All beam and column load data pertains to carbon steel and stainless steel channels. Load tables and charts are constructed to be in accordance with the SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007 EDITION published by the AMERICAN IRON AND STEEL INSTITUTE USING ASD METHOD. Loads are based on 33 ksi steel cold formed to 42 ksi.

Type of Load Safety Factor to Yield Strength Safety Factor to Ultimate Strength
Beam Loads 1.67 2.0
Column Loads 1.80 2.2

P3300 - BEAM LOADING

Uniform Loading at Deflection
Span (In) Max Allowable Uniform Load (Lbs) Deflection at Uniform Load (In) Span/180 (Lbs) Span/240 (Lbs) Span/360 (Lbs)
24 600 0.10 600 600 400
36 400 0.22 360 270 180
48 300 0.40 200 150 100
60 240 0.62 130 100 60
72 200 0.89 90 70 40
84 170 1.20 70 50 30
96 150 1.59 50 40 30
108 130 1.96 40 30 20
120 120 2.48 30 20 20

 

P3300 - COLUMN LOADING

Maximum Column Load Applied at C.G.
Unbraced Height (In) Max Allowable Load at Slot Face (Lbs) K = 0.65
(Lbs)
K = 0.80
(Lbs)
K = 1.0
(Lbs)
K = 1.2
(Lbs)
24 2360 7740 7260 6350 5390
36 2120 6470 5390 3990 2810
48 1760 4910 3550 2270 1580
60 1380 3440 2270 1460 **
72 1080 2390 1550 ** **

 

Notes:
* Load limited by spot weld shear.
** KL⁄r > 200
NR = Not Recommended.
1. Beam loads are given in total uniform load (W Lbs) not uniform load (w lbs/ft or
w lbs/in).
2. Beam loads are based on a simple span and assumed to be adequately laterally
braced. Unbraced spans can reduce beam load carrying capacity. Refer to Page 62
for reduction factors for unbraced lengths.
3. For pierced channel, multiply beam loads by the following factor:
"KO" Series........95%    "T" Series...........85%
"HS" Series........90%    "SL" Series.........85%
"H3" Series.........90%   "DS" Series........70%
"WT" Series........85%
4. Deduct channel weight from the beam loads.
5. For concentrated midspan point loads, multiply beam loads by 50% and the
corresponding deflection by 80%. For other load conditions refer to page 18.
6. All beam loads are for bending about Axis 1-1.
Parameter P3300 P3301
Area of Section 0.395 In² 0.790 In²
Axis 1-1          
  Moments of Inertia (I) 0.037 In⁴ 0.176 In⁴
  Section Modulus (S) 0.072 In³ 0.201 In³
  Rdius of Gyration (r) 0.306 In 0.472 In
Axis 2-2          
  Moments of Inertia (I) 0.143  In⁴ 0.285 In⁴
  Section Modulus (S) 0.176  In³ 0.351 In³
  Rdius of Gyration (r) 0.601  In 0.601 In

Get your free copy of the Unistrut No. 17 General Engineering Catalog

Save paper! Download the most up to date version of Unistrut's General Engineering Catalog, right here, in digital format.

  • Unistrut Part Numbers
  • Product specifications
  • Engineering Data
  • Load Tables
  • Product Finish Information,
  • and more!
Unistrut-Catalog-17

*Please note, catalog is in PDF format. You must have Adobe Reader (a FREE and trusted program) installed, to view. If you do not already have Adobe Reader installed, you may download it from Adobe's website. *Download times may vary, file is large.*

Save paper! Download the most up to date version of Unistrut's General Engineering Catalog, right here, in digital format.

Write Your Own Review
You're reviewing:Unistrut P3300T 1-5/8'' x 7/8'' Slotted Channel, 12 Gauge