UNISTRUT P4101 1-5/8" x 1-5/8" Double Channel, 14 Gauge

Sku:

P4101

UOM: LGT

Product Details

Unistrut's P4101 (back-to-back solid) channel is our 14 gauge channel that is commonly used for trapeze supports, seismic bracing, ceiling grids, pipe, conduit, duct and cable tray supports, racks, and other general framing. For application examples, refer to our Application Showcase.

A 14 gage product is appealing to users who feel the 12 gauge alternatives provide an excess loading capacities than what is required from the design. It is also UL listed and CSA listed for use as a strut-type channel raceway.

Product dimensions are 1 5/8" wide x 1 5/8" tall x 14 ga. thick, solid. Punched holes are also available for ease of installation.

Our P4101 is available in the following finishes: Pre-Galvanized (PG), Unistrut Defender (DF), Hot-Dip Galvanized (HG), Plain (PL), Green (GR), Stainless Steel (SS or ST) and Aluminum (EA).


Unistrut Buffalo is a division of Eberl Iron Works, Inc.

 

     

More Information
Pricing SKU P4101-10PL
SKU P4101
Pack Size Length
UOM LGT
Brand Unistrut

MATERIAL

Unistrut channels are accurately and carefully cold formed to size from low-carbon strip steel.

All spot-welded combination members, except P1001T, are welded 3" (76 mm) maximum on center.

STEEL: PLAIN

12 Ga. (2.7 mm), 14 Ga.(1.9 mm) and
16 Ga. (1.5 mm) ASTM A1011 SS GR 33

STEEL: PRE-GALVANIZED

12 Ga. (2.7 mm), 14 Ga. (1.9 mm) and
16 Ga. (1.5mm) ASTM A653 GR 33

For other materials, see Special Metals or Fiberglass sections.

FINISHES

All channels are available in:

  • Perma Green III (GR)
  • Pre-galvanized (PG), conforming to ASTM A653 G90
  • Hot-dipped galvanized (HG), conforming to ASTM A123
  • Plain (PL)
  • Unistrut Defender™ (DF), conforming to ASTM A1046

*** Perma Green finish is a commercial grade finish, and as such scuffs and scratch marks are to be expected. If a flawless finish is desired, it is recommended to apply a matching touch up paint ***

DIMENSIONS

Imperial dimensions are illustrated in inches. Metric dimensions are shown in millimeters and rounded to one decimal place.

STANDARD LENGTHS

Standard lengths are 10 feet (3.05m) and 20 feet (6.10m). Tolerances are ±1⁄8" (3 mm). Special lengths are available for a small cutting charge with a tolerance of ±1⁄8" (3 mm).

CURVED CHANNEL

Contact your local Unistrut Service Center or Unistrut Corporation for more information.

LOAD DATA

All beam and column load data pertains to carbon steel and stainless steel channels. Load tables and charts are constructed to be in accordance with the SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007 EDITION published by the AMERICAN IRON AND STEEL INSTITUTE USING ASD METHOD. Loads are based on 33 ksi steel cold formed to 42 ksi.

Type of Load Safety Factor to Yield Strength Safety Factor to Ultimate Strength
Beam Loads 1.67 2.0
Column Loads 1.80 2.2

P4100 - BEAM LOADING

Uniform Loading at Deflection Lateral
Bracing
Reduction
Factor

Span (In) Max Allowable Uniform Load (Lbs) Deflection at Uniform Load (In) Span/180 (Lbs) Span/240 (Lbs) Span/360 (Lbs)
24 * 1090 0.06 * 1090 * 1090 * 1090 1.00
36 800 0.14 800 800 570 1.00
48 600 0.25 600 480 320 1.00
60 480 0.39 410 310 200 0.96
72 400 0.57 280 210 140 0.92
84 340 0.76 210 160 100 0.89
96 300 1.00 160 120 80 0.85
108 270 1.29 130 90 60 0.81
120 240 1.57 100 80 50 0.78
144 200 2.26 70 50 40 0.71
168 170 3.05 50 40 30 0.64
192 150 4.02 40 NR NR 0.57
216 130 4.96 NR NR NR 0.50
240 120 6.28 NR NR NR 0.45

Note: NR - Not Recommended

Note: * Load limited by weld shear

 

P4100 - COLUMN LOADING

Maximum Column Load Applied at C.G.
Unbraced Height (In) Max Allowable Load at Slot Face (Lbs) K = 0.65
(Lbs)
K = 0.80
(Lbs)
K = 1.0
(Lbs)
K = 1.2
(Lbs)
24 3240 12370 11950 11370 10540
36 3120 11470 10540 9160 7720
48 2940 10090 8680 6770 4980
60 2680 8560 6770 4590 3190
72 2310 7010 4980 3190 2200
  1950 5530 3660 2340 KL/r>200
96 1650 4250 2800 KL/r>200 KL/r>200
108 1410 3360 2200 KL/r>200 KL/r>200

 

Notes:
* Load limited by spot weld shear.
** KL⁄r > 200
NR = Not Recommended.
1. Beam loads are given in total uniform load (W Lbs) not uniform load (w lbs/ft or
w lbs/in).
2. Beam loads are based on a simple span and assumed to be adequately laterally
braced. Unbraced spans can reduce beam load carrying capacity. Refer to Page 62
for reduction factors for unbraced lengths.
3. For pierced channel, multiply beam loads by the following factor:
"KO" Series........95%    "T" Series...........85%
"HS" Series........90%    "SL" Series.........85%
"H3" Series.........90%   "DS" Series........70%
"WT" Series........85%
4. Deduct channel weight from the beam loads.
5. For concentrated midspan point loads, multiply beam loads by 50% and the
corresponding deflection by 80%. For other load conditions refer to page 18.
6. All beam loads are for bending about Axis 1-1.

Get your free copy of the Unistrut No. 17 General Engineering Catalog

Save paper! Download the most up to date version of Unistrut's General Engineering Catalog, right here, in digital format.

  • Unistrut Part Numbers
  • Product specifications
  • Engineering Data
  • Load Tables
  • Product Finish Information,
  • and more!
Unistrut-Catalog-17

*Please note, catalog is in PDF format. You must have Adobe Reader (a FREE and trusted program) installed, to view. If you do not already have Adobe Reader installed, you may download it from Adobe's website. *Download times may vary, file is large.*

Save paper! Download the most up to date version of Unistrut's General Engineering Catalog, right here, in digital format.

Write Your Own Review
You're reviewing:UNISTRUT P4101 1-5/8" x 1-5/8" Double Channel, 14 Gauge